Look up R-134a saturation pressure or temperature, or scan the full chart below. R-134a is a single-component refrigerant, so one pressure column covers both superheat and subcooling.
Gauge pressure at sea level. R-134a is a single-component refrigerant, so liquid and vapor saturate at the same pressure. Values marked inHg are vacuum, in inches of mercury.
°Fpsig
°Fpsig
°Fpsig
°Fpsig
°Fpsig
°Fpsig
R-134a saturation pressure by temperature, °F and psig
°F
psig
-40
14.8 inHg
-39
14.4 inHg
-38
13.9 inHg
-37
13.4 inHg
-36
13.0 inHg
-35
12.5 inHg
-34
12.0 inHg
-33
11.4 inHg
-32
10.9 inHg
-31
10.4 inHg
-30
9.8 inHg
-29
9.3 inHg
-28
8.7 inHg
-27
8.1 inHg
-26
7.5 inHg
-25
6.9 inHg
-24
6.3 inHg
-23
5.7 inHg
-22
5.0 inHg
-21
4.3 inHg
-20
3.7 inHg
-19
3.0 inHg
-18
2.3 inHg
-17
1.5 inHg
-16
0.8 inHg
-15
0.1 inHg
-14
0.4
-13
0.7
-12
1.1
-11
1.5
-10
1.9
-9
2.4
-8
2.8
-7
3.2
-6
3.6
-5
4.1
-4
4.6
-3
5.0
-2
5.5
-1
6.0
0
6.5
1
7.0
2
7.5
3
8.0
4
8.5
5
9.1
6
9.6
7
10.2
8
10.8
9
11.3
10
11.9
11
12.5
12
13.1
13
13.8
14
14.4
15
15.0
16
15.7
17
16.4
18
17.0
19
17.7
20
18.4
21
19.1
22
19.9
23
20.6
24
21.3
25
22.1
26
22.9
27
23.7
28
24.5
29
25.3
30
26.1
31
26.9
32
27.8
33
28.6
34
29.5
35
30.4
36
31.3
37
32.2
38
33.1
39
34.1
40
35.0
41
36.0
42
37.0
43
38.0
44
39.0
45
40.1
46
41.1
47
42.2
48
43.2
49
44.3
50
45.4
51
46.6
52
47.7
53
48.9
54
50.0
55
51.2
56
52.4
57
53.6
58
54.9
59
56.1
60
57.4
61
58.7
62
60.0
63
61.3
64
62.7
65
64.0
66
65.4
67
66.8
68
68.2
69
69.7
70
71.1
71
72.6
72
74.1
73
75.6
74
77.1
75
78.7
76
80.2
77
81.8
78
83.4
79
85.0
80
86.7
81
88.4
82
90.0
83
91.8
84
93.5
85
95.2
86
97.0
87
98.8
88
100.6
89
102.5
90
104.3
91
106.2
92
108.1
93
110.0
94
112.0
95
113.9
96
115.9
97
118.0
98
120.0
99
122.1
100
124.2
101
126.3
102
128.4
103
130.6
104
132.7
105
135.0
106
137.2
107
139.5
108
141.7
109
144.0
110
146.4
111
148.7
112
151.1
113
153.5
114
156.0
115
158.4
116
160.9
117
163.4
118
166.0
119
168.6
120
171.2
121
173.8
122
176.5
123
179.1
124
181.8
125
184.6
126
187.4
127
190.1
128
193.0
129
195.8
130
198.7
131
201.6
132
204.6
133
207.5
134
210.6
135
213.6
136
216.7
137
219.7
138
222.9
139
226.0
140
229.2
141
232.4
142
235.7
143
239.0
144
242.3
145
245.7
146
249.0
147
252.5
148
255.9
149
259.4
150
262.9
°CkPa
°CkPa
°CkPa
°CkPa
°CkPa
°CkPa
R-134a saturation pressure by temperature, °C and kPa
°C
kPa
-40
-50
-39
-47
-38
-45
-37
-42
-36
-38
-35
-35
-34
-32
-33
-28
-32
-25
-31
-21
-30
-17
-29
-13
-28
-9
-27
-4
-26
0
-25
5
-24
10
-23
15
-22
20
-21
26
-20
31
-19
37
-18
43
-17
50
-16
56
-15
63
-14
69
-13
77
-12
84
-11
91
-10
99
-9
107
-8
116
-7
124
-6
133
-5
142
-4
151
-3
161
-2
171
-1
181
0
191
1
202
2
213
3
225
4
236
5
248
6
261
7
273
8
286
9
300
10
313
11
327
12
342
13
356
14
372
15
387
16
403
17
419
18
436
19
453
20
470
21
488
22
507
23
525
24
544
25
564
26
584
27
605
28
626
29
647
30
669
31
691
32
714
33
737
34
761
35
786
36
811
37
836
38
862
39
888
40
915
41
943
42
971
43
1,000
44
1,029
45
1,059
46
1,089
47
1,120
48
1,152
49
1,184
50
1,217
51
1,250
52
1,284
53
1,319
54
1,354
55
1,390
56
1,427
57
1,464
58
1,502
59
1,541
60
1,580
61
1,621
62
1,661
63
1,703
64
1,745
65
1,788
You're free to reuse this chart's numbers under CC BY 4.0. Just credit Pocket HVAC and link back to this page.
From pockethvac.com/r134a-pt-chart/. Each row is solved at its exact temperature with CoolProp 8.0.0. Free to reuse under CC BY 4.0.
What is an R-134a PT chart?
An R-134a PT chart lists the pressure R-134a boils and condenses at for each temperature. At 40°F that's just 35.0 psig, and below about -15°F it drops into a vacuum. It's a single-component refrigerant sold as Freon 134a, Forane 134a, Genetron 134a and Klea 134a.
Anywhere liquid and vapor are together in a system, like inside the evaporator and condenser coils, the pressure and temperature are locked together, so one tells you the other. On the job, the chart turns gauge readings into saturation temperatures: the suction pressure gives the temperature the evaporator is boiling at, and the liquid line pressure gives the temperature the condenser is condensing at. Compare those with your line temperatures and you have superheat and subcooling.
R-134a is a single-component refrigerant (safety class A1) that runs at much lower pressures than R-410A. In HVAC you'll mostly find it in chillers, and it was the standard refrigerant in car air conditioning for years.
How it's calculated
Absolute pressure = gauge pressure + 14.696 psi (101.325 kPa, one standard atmosphere)
Saturation data: R-134a: CoolProp 8.0.0, R134a
Between table points (every 0.5 °C): ln(pressure) is interpolated linearly in 1 ÷ absolute temperature
Printed chart rows are solved by CoolProp at each exact temperature
If a number doesn't match your chart, email me what you entered and what you expected, and I'll check it against the source. You can also read how the numbers are checked.
R-134a's saturation pressure at 40°F is 35.0 psig. At 100°F it's 124.2 psig.
Why does the chart show inHg at low temperatures?
Below about -15°F, R-134a's saturation pressure is under atmospheric, so a gauge reads a vacuum. The chart shows those rows in inches of mercury, like a compound gauge.
How accurate is this chart?
It comes from the NIST equation of state for R-134a through CoolProp, and matches NIST's own tables to within 0.01 psi.